These con-figurations can be changed using the accessory BACview6 display. Navigation: BACviewĺCCN Home: Element Comm Stat Element: 1 Bus: 0 Troubleshooting — If there are problems wiring or ad-dressing the UPC Open controller, contact Carrier Technical Support.. The UPC Open can convert proprietary equipment data into open protocol data, enabling a stand-alone, single piece of equipment to reside on a BACnet network, where it can be monitored or controlled by a Building Automation System (BAS).
An i-Vu® Link/Open Link can reference a third-party BACnet point on any network type if a BACnet route to the point exists. NOTE Communication may be affected by the network bandwidth as well as the frequency and number of points communicating.. The UPC Open's two rotary switches determine the UPC Open's MAC address when it is placed on an MS/TP or ARCNET network. The rotary switches define the MAC address portion of the UPC Open's BACnet device instance number, which is composed of the MS/TP or ARCNET network number and the MAC address.